Steel Pipes and Heat Loss Diagram

Heat loss from 1/2" to 12" steel pipes at various temperature differences between pipe and surrounding air are indicated in the diagram and table below:

 

Heat loss from Fluid inside Pipe (W/m) 

Nominal bore

Temperature Difference (oC)

(mm)

(inch)

50

60

75

100

110

125

140

150

165

195

225

280

15

1/2

30

40

60

90

130

155

180

205

235

280

375

575

20

3/4

35

50

70

110

160

190

220

255

290

370

465

660

25

1

40

60

90

130

200

235

275

305

355

455

565

815

32

1 1/4

50

70

110

160

240

290

330

375

435

555

700

1000

40

1 1/2

55

80

120

180

270

320

375

420

485

625

790

1120

50

2

65

95

150

220

330

395

465

520

600

770

975

1390

65

2 1/2

80

120

170

260

390

465

540

615

715

910

1150

1650

80

3

100

140

210

300

470

560

650

740

860

1090

1380

1980

100

4

120

170

260

380

585

700

820

925

1065

1370

1740

2520

150

6

170

250

370

540

815

970

1130

1290

1470

1910

2430

3500

200

8

220

320

470

690

1040

1240

1440

1650

1900

2440

3100

4430

250

10

270

390

570

835

1250

1510

1750

1995

2300

2980

3780

5600

300

12

315

460

670

980

1470

1760

2060

2340

2690

3370

4430

6450

 

The heat loss value must be corrected by the correction factor for certain applications:

 

Application

Correction factor

Single pipe freely exposed

1.1

More than one pipe freely exposed

1.0

More than one pipe along the ceiling

0.65

Single pipe along skirting or riser

1.0

More than one pipe along skirting or riser

0.90

Single pipe along ceiling

0.75